range | ComPact |
---|---|
product name | ComPact NSX |
range of product | ComPact NSX100...250 |
device short name | NSX250F |
product or component type | Circuit breaker |
device application | Distribution |
Number of poles | 3P |
protected poles description | 3t |
[In] rated current | 200 A at 40 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
network type | AC |
network frequency | 50/60 Hz |
suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity | 85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 600 V AC 50/60 Hz conforming to UL 508 |
Performance level | F 36 kA 415 V AC |
trip unit name | TM-D |
trip unit technology | Thermal-magnetic |
trip unit protection functions | LI |
control type | Toggle |
Circuit breaker mounting mode | Fixed |
[Ui] rated insulation voltage 800 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 8 kV [Ics] rated service short-circuit breaking capacity 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2mechanical durability 20000 cycles electrical durability 5000 cycles at 690 V In
10000 cycles at 690 V In/2
10000 cycles at 440 V In
20000 cycles at 440 V In/2mounting support Backplate upside connection Front downside connection Front connection pitch 35 mm protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)trip unit rating 200 A at 40 °C Long-time pick-up adjustment type Ir (thermal protection) Adjustable [Ir] long-time protection pick-up adjustment range 0.7...1 x In Long-time protection delay adjustment type tr Fixed [tr] long-time protection delay adjustment range 120…400 s at 1.5 x In
15 s at 6 x IrShort-time protection pick-up adjustment type Isd Adjustable [Isd] Short-time protection pick-up adjustment range 5...10 x In Short-time protection delay adjustment type tsd Fixed earth-leakage protection Without Number of slots for electrical auxiliaries 5 slot(s) Width (W) 105 mm Height (H) 161 mm Depth (D) 86 mm net weight 2.4 kg standards EN/IEC 60947 product certifications Marine
CCC
EACovervoltage category Class II electrical shock protection class Class II pollution degree 3 conforming to IEC 60664-1 IP degree of protection IP40 conforming to IEC 60529 IK degree of protection IK07 conforming to IEC 62262 ambient air temperature for operation -25…70 °C ambient air temperature for storage -50…85 °C relative humidity 0…95 % operating altitude 0...2000 m without derating
2000 m...5000 m with deratingUnit Type of Package 1 PCE Package 1 Length 19 cm Number of Units in Package 1 1 Package 2 Width 40 cm Package 2 Height 30 cm Package 2 Weight 24.802 kg Package 1 Width 11.5 cm Package 1 Height 14 cm Package 1 Weight 2.003 kg Number of Units in Package 2 12 Unit Type of Package 2 S04 Package 2 Length 60 cm