Product Filter
range | ComPact |
---|---|
product name | ComPact NSX |
range of product | ComPact NSX400...630 |
device short name | NSX400N |
product or component type | Circuit breaker |
device application | Distribution |
Number of poles | 3P |
protected poles description | 3t |
[In] rated current | 400 A at 40 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
network type | AC |
network frequency | 50/60 Hz |
suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity | 85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 600 V AC 50/60 Hz conforming to UL 508 50 kA at 480 V AC 50/60 Hz conforming to UL 508 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance level | N 50 kA 415 V AC |
trip unit name | Micrologic 5.3 A |
trip unit technology | Electronic |
trip unit protection functions | LSI |
control type | Toggle |
Circuit breaker mounting mode | Fixed |
[Ui] rated insulation voltage 800 V AC 50/60 Hz [Uimp] rated impulse withstand voltage 8 kV [Ics] rated service short-circuit breaking capacity 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2mechanical durability 15000 cycles electrical durability 3000 cycles at 690 V In
6000 cycles at 690 V In/2
6000 cycles at 440 V In
12000 cycles at 440 V In/2mounting support Backplate upside connection Front downside connection Front connection pitch 45 mm protection type L : for overload protection (long time)
S : for short time short-circuit protection
I : for instantaneous short-circuit protectiontrip unit rating 400 A at 40 °C Long-time pick-up adjustment type Ir (thermal protection) Adjustable [Ir] long-time protection pick-up adjustment range 160...400 A Long-time protection delay adjustment type tr Adjustable [tr] long-time protection delay adjustment range 15…400 s at 1.5 x Ir
0.35…11 s at 7.2 x Ir
0.5…16 s at 6 x Irthermal memory 20 minutes before and after tripping Short-time protection pick-up adjustment type Isd Adjustable [Isd] Short-time protection pick-up adjustment range 1.5...10 x Ir Short-time protection delay adjustment type tsd Adjustable [tsd] Short-time protection delay adjustment range 0…0.4 s Instantaneous protection pick-up adjustment type Ii Adjustable [Ii] instantaneous protection pick-up adjustment range 1.5...12 x In earth-leakage protection Without zone selective interlocking ZSI With Number of slots for electrical auxiliaries 6 slot(s) local signalling Flashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overloaddisplay type LCD display type of measurement Ammeter communication of data Energy metering
Maximeters/minimeters
Demand current and power
Instantaneous and demand values
Protection and alarm settings
Maintenance indicators
Power quality
Time-stamped histories and event tablesWidth (W) 140 mm Height (H) 255 mm Depth (D) 110 mm net weight 6.05 kg standards EN/IEC 60947 product certifications CCC
EAC
Marineovervoltage category Class II electrical shock protection class Class II pollution degree 3 conforming to IEC 60664-1 IP degree of protection IP40 conforming to IEC 60529 IK degree of protection IK07 conforming to IEC 62262 ambient air temperature for operation -25…70 °C ambient air temperature for storage -40…85 °C relative humidity 0…95 % operating altitude 0...2000 m without derating
2000 m...5000 m with derating