VitalMRO is Authorized Distributor for This Product.
range of product | Altivar 212 |
---|---|
product or component type | Variable speed drive |
device short name | ATV212 |
product destination | Asynchronous motors |
product specific application | Pumps and fans in HVAC |
assembly style | With heat sink |
network number of phases | 3 phases |
motor power kW | 3 kW |
motor power hp | 4 hp |
[Us] rated supply voltage | 380...480 V - 15...10 % |
supply voltage limits | 323…528 V |
supply frequency | 50...60 Hz - 5...5 % |
EMC filter | Class C2 EMC filter integrated |
line current | 4.9 A at 480 V 6.2 A at 380 V |
apparent power 5.5 kVA at 380 V prospective line Isc 5 kA continuous output current 7.2 A at 380 V
7.2 A at 460 Vmaximum transient current 7.9 A for 60 s speed drive output frequency 0.5…200 Hz nominal switching frequency 12 kHz switching frequency 6...16 kHz adjustable
12...16 kHz with derating factorspeed range 1…10 speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn torque accuracy +/- 15 % transient overtorque 120 % of nominal motor torque +/- 10 % for 60 s asynchronous motor control profile Voltage/frequency ratio, 2 points
Voltage/frequency ratio, 5 points
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Voltage/frequency ratio - Energy Saving, quadratic U/f
Flux vector control without sensor, standardregulation loop Adjustable PI regulator motor slip compensation Adjustable
Automatic whatever the load
Not available in voltage/frequency ratio motor controllocal signalling 1 LED (red) for DC bus energized output voltage <= power supply voltage isolation Electrical between power and control type of cable Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVCelectrical connection VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
L1/R, L2/S, L3/T: terminal 6 mm² / AWG 10tightening torque 1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T)
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)supply Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protectionanalogue input number 2 analogue input type VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm
VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bitssampling duration 2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analogresponse time FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)accuracy +/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °Clinearity error VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
FM: +/- 0.2 % for outputanalogue output number 1 analogue output type FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bitsdiscrete output number 2 discrete output type Configurable relay logic: (FLA, FLC) NO - 100000 cycles
Configurable relay logic: (FLB, FLC) NC - 100000 cycles
Configurable relay logic: (RY, RC) NO - 100000 cyclesminimum switching current 3 mA at 24 V DC for configurable relay logic maximum switching current 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)discrete input type F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohmdiscrete input logic Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)acceleration and deceleration ramps Automatic based on the load
Linear adjustable separately from 0.01 to 3200 sbraking to standstill By DC injection protection type Overheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overvoltages on the DC bus: drive
Break on the control circuit: drive
Against exceeding limit speed: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor
Motor phase break: motor
With PTC probes: motordielectric strength 3535 V DC between earth and power terminals
5092 V DC between control and power terminalsinsulation resistance >= 1 mOhm 500 V DC for 1 minute frequency resolution Display unit: 0.1 Hz
Analog input: 0.024/50 Hzcommunication port protocol METASYS N2
LonWorks
Modbus
BACnet
APOGEE FLNconnector type 1 open style
1 RJ45physical interface 2-wire RS 485 transmission frame RTU transmission rate 9600 bps or 19200 bps data format 8 bits, 1 stop, odd even or no configurable parity type of polarization No impedance number of addresses 1…247 communication service Write multiple registers (16) 2 words maximum
Read holding registers (03) 2 words maximum
Time out setting from 0.1 to 100 s
Read device identification (43)
Monitoring inhibitable
Write single register (06)option card Communication card for LonWorks operating position Vertical +/- 10 degree width 142 mm height 184 mm depth 150 mm net weight 3.35 kg power dissipation in W 137 W air flow 47 m3/h functionality Mid specific application HVAC IP degree of protection IP21 Variable speed drive application selection Building - HVAC Compressor for scroll
Building - HVAC Fan
Building - HVAC PumpMotor power range AC-3 2.2…3 kW at 380…440 V 3 phases
2.2…3 kW at 480…500 V 3 phasesmotor starter type Variable speed drive
Comments